Source
us-cert
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v3 7.5 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: SIMATIC CP, SINAMICS, SIPLUS NET CP Vulnerability: Missing Release of Memory after Effective Lifetime 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an unauthorized attacker with network access to the web server of an affected device to perform a denial-of-service attack. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following products of Siemens, are affected: SIMATIC CP 1242-7 V2 (incl. SIPLUS variants): All versions SIMATIC CP 1243-1 (incl. SIPLUS variants): All versions SIMATIC CP 1243-1 DNP3 (incl. SIPLUS variants): All...
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v3 7.5 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: User Management Component (UMC) Vulnerabilities: Permissive Cross-domain Policy with Untrusted Domains, Cross-site Scripting, Classic Buffer Overflow, Improper Input Validation 2. RISK EVALUATION Successful exploitation of these vulnerabilities could lead to a restart of the UMC server. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Siemens reports the following products are affected: Opcenter Quality: all versions SIMATIC PCS neo: versions prior to v4.1 SINUMERIK Integrate RunMyHMI /Automotive: all versions Totally Integrated Automation Portal (TIA Portal) v...
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v3 7.5 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: SINUMERIK MC, SINUMERIK ONE Vulnerability: Integer Overflow or Wraparound 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an unauthenticated remote attacker to create a denial of service condition by sending a specially crafted certificate. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following products of Siemens, are affected: SINUMERIK MC: All versions prior to V1.22 SINUMERIK ONE: All versions prior to V6.22 3.2 Vulnerability Overview 3.2.1 INTEGER OVERFLOW OR WRAPAROUND CWE-190 The OPC UA implementations (ANSI C and C++...
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v3 7.6 ATTENTION: Low Attack Complexity Vendor: Siemens Equipment: LOGO! and SIPLUS LOGO! Products Vulnerability: Improper Protection against Electromagnetic Fault Injection (EM-FI) 2. RISK EVALUATION Successful exploitation of this vulnerability could cause an electromagnetic fault injection, which would allow an attacker to dump and debug the firmware including memory manipulation. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following products of Siemens, are affected: LOGO! 12/24RCE (6ED1052-1MD08-0BA1): Versions v8.3 and prior LOGO! 12/24RCEo (6ED1052-2MD08-0BA1): Versions v8.3 and prior LOGO! 24CE (6ED1052-1CC08-0BA1): Versions v8.3 ...
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v3 4.2 ATTENTION: Low attack complexity Vendor: Siemens Equipment: SIMATIC STEP 7 (TIA Portal) Vulnerability: Cleartext Storage of Sensitive Information in Memory 2. RISK EVALUATION Successful exploitation of this vulnerability could allow a local attacker to gain access to the access level password of the SIMATIC S7-1200 and S7-1500 CPUs, when entered by a legitimate user in the hardware configuration of the affected application. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following Siemens product is affected: SIMATIC STEP 7 (TIA Portal): All versions prior to V19 3.2 Vulnerability Overview 3.2.1 CLEARTEXT STORAGE OF SENSITIVE INFORMATI...
View CSAF 1. EXECUTIVE SUMMARY CVSS v3 7.5 ATTENTION: Exploitable from adjacent network Vendor: Sensormatic Electronics, LLC, an affiliate of Johnson Controls Inc. Equipment: Kantech Gen1 ioSmart card reader Vulnerability: Missing Release of Memory after Effective Lifetime 2. RISK EVALUATION An attacker with physical access to the Kantech Gen1 ioSmart card reader in certain circumstances can recover the reader's communication memory between the card and reader. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Kantech Gen1 ioSmart card reader are affected: Kantech Gen1 ioSmart card reader: firmware versions prior to 1.7.2 3.2 Vulnerability Overview 3.2.1 MISSING RELEASE OF MEMORY AFTER EFFECTIVE LIFETIME CWE-401 Kantech Gen1 ioSmart card readers with firmware versions prior to 1.7.2 do not properly release memory after its effective lifetime. An attacker with physical access to the Kantech Gen1 ioSmart card reader in certain circumstances can recover the reader's com...
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v3 7.5 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: SIMATIC and SIPLUS products Vulnerabilities: Uncontrolled Recursion, Buffer Access with Incorrect Length Value 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an unauthorized attacker with network access to the web server to perform a denial-of-service attack. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following products of Siemens, are affected: SIMATIC S7-400 CPU 412-2 PN V7 (6ES7412-2EK07-0AB0): All versions SIMATIC S7-400 CPU 414-3 PN/DP V7 (6ES7414-3EM07-0AB0): All versions SIMATIC S7-400 CPU 414F-3 PN/DP V7 (6ES74...
View CSAF 1. EXECUTIVE SUMMARY CVSS v3 5.3 ATTENTION: Vendor: Schneider Electric Equipment: Easy UPS Online Monitoring Software Vulnerability: Path Traversal 2. RISK EVALUATION Successful exploitation of this vulnerability could allow elevation of privileges which could result in arbitrary file deletion with system privileges. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Schneider Electric reports that the following versions of Easy UPS Online Monitoring Software are affected: Easy UPS Online Monitoring Software (Windows 10, 11, Windows 3.2 Vulnerability Overview 3.2.1 Path Traversal CWE-22 A path traversal vulnerability exists that could cause arbitrary file deletion upon service restart when accessed by a local and low-privileged attacker. CVE-2023-6407 has been assigned to this vulnerability. A CVSS v3.1 base score of 5.3 has been calculated; the CVSS vector string is (AV:L/AC:H/PR:L/UI:N/S:U/C:N/I:L/A:H). 3.3 BACKGROUND CRITICAL INFRASTRUCTURE SECTORS: Multiple COUNTRIES/AREAS DEPLOY...
View CSAF 1. EXECUTIVE SUMMARY CVSS v3 5.3 ATTENTION: Vendor: Schneider Electric Equipment: Easy UPS Online Monitoring Software Vulnerability: Path Traversal 2. RISK EVALUATION Successful exploitation of this vulnerability could allow elevation of privileges which could result in arbitrary file deletion with system privileges. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Schneider Electric reports that the following versions of Easy UPS Online Monitoring Software are affected: Easy UPS Online Monitoring Software (Windows 10, 11, Windows 3.2 Vulnerability Overview 3.2.1 Path Traversal CWE-22 A path traversal vulnerability exists that could cause arbitrary file deletion upon service restart when accessed by a local and low-privileged attacker. CVE-2023-6407 has been assigned to this vulnerability. A CVSS v3.1 base score of 5.3 has been calculated; the CVSS vector string is (AV:L/AC:H/PR:L/UI:N/S:U/C:N/I:L/A:H). 3.3 BACKGROUND CRITICAL INFRASTRUCTURE SECTORS: Multiple COUNTRIES/AREAS DEPLOY...
View CSAF 1. EXECUTIVE SUMMARY CVSS v3 7.5 ATTENTION: Exploitable remotely/low attack complexity Vendor: Johnson Controls Equipment: Metasys and Facility Explorer Vulnerability: Uncontrolled Resource Consumption 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to cause a denial-of-service by sending invalid credentials. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Johnson Controls Metasys and Facility Explorer are affected: Metasys NAE55 engines: Versions prior to 12.0.4 Metasys SNE engines: Versions prior to 12.0.4 Metasys SNC engines: Versions prior to 12.0.4 Facility Explorer F4-SNC: Versions prior to 11.0.6 Facility Explorer F4-SNC: Versions prior to 12.0.4 3.2 Vulnerability Overview 3.2.1 UNCONTROLLED RESOURCE CONSUMPTION CWE-400 Under certain circumstances, invalid authentication credentials could be sent to the login endpoint of Johnson Controls Metasys and Facility Explorer products to cause denial-of-service. CVE-...